COMMISSION IMPLEMENTING REGULATION (EU) 2023/2727
of 30 November 2023
granting a Union authorisation for the single biocidal product ‘PPC Chlorine liquid’
(Text with EEA relevance)
Article 1
Article 2
ANNEX
Summary of product characteristics for a biocidal product
1.
ADMINISTRATIVE INFORMATION
1.1.
Trade name(s) of the product
Trade name(s) |
PPC Chlorine Liquid |
1.2.
Authorisation holder
Name and address of the authorisation holder |
Name |
Vynova PPC SAS |
Address |
95 rue du Général de Gaulle BP 60090, 68802 THANN CEDEX France |
|
Authorisation number |
EU-0027045-0000 |
|
R4BP asset number |
EU-0027045-0000 |
|
Date of the authorisation |
27 December 2023 |
|
Expiry date of the authorisation |
30 April 2033 |
1.3.
Manufacturer(s) of the product
Name of manufacturer |
Vynova PPC SAS |
Address of manufacturer |
95 rue du Général de Gaulle, 68802 Thann Cedex France |
Location of manufacturing sites |
95 rue du Général de Gaulle, 68802 Thann Cedex France |
1.4.
Manufacturer(s) of the active substance(s)
Active substance |
Active chlorine released from chlorine |
Name of manufacturer |
Vynova PPC SAS |
Address of manufacturer |
95 rue du Général de Gaulle, 68802 Thann Cedex France |
Location of manufacturing sites |
95 rue du Général de Gaulle, 68802 Thann Cedex France |
2.
PRODUCT COMPOSITION AND FORMULATION
2.1.
Qualitative and quantitative information on the composition of the product
Common name |
IUPAC name |
Function |
CAS number |
EC number |
Content (%) |
Active chlorine released from chlorine |
|
Active Substance |
|
|
100,0 |
chlorine |
chlorine |
Non-active substance |
7782-50-5 |
231-959-5 |
100,0 |
2.2.
Type of formulation
3.
HAZARD AND PRECAUTIONARY STATEMENTS
Hazard statements |
May cause or intensify fire; oxidiser Causes skin irritation. Causes serious eye irritation. Toxic if inhaled. May cause respiratory irritation. Very toxic to aquatic life. Contains gas under pressure; may explode if heated |
Precautionary statements |
Keep away from clothing and other combustible materials. Do not breathe gas. Avoid release to the environment. Wear protective gloves. Wear protective clothing. Wear eye protection. Wear face protection. IF INHALED:Remove person to fresh air and keep comfortable for breathing. IF IN EYES:Rinse cautiously with water for several minutes.Remove contact lenses, if present and easy to do. Continue rinsing. Collect spillage. Store in a well-ventilated place.Keep container tightly closed. Store locked up. Protect from sunlight.Store in a well-ventilated place. In case of fire:Stop leak if safe to do so. Dispose of contents to local regulation. Keep valves and fittings free from oil and grease. Call a doctor if you feel unwell. Avoid breathing gas. Wash hands thoroughly after handling. Use only outdoors or in a well-ventilated area. IF ON SKIN:Wash with plenty of water. Call a Poison center/doctor. Specific treatment (see reference to supplemental first aid instruction on this label). If skin irritation occurs:Get medical attention. If eye irritation persists:Get medical attention. Take off contaminated clothing.And wash it before reuse. |
4.
AUTHORISED USE(S)
4.1.
Use description
Product type |
PT02 - Disinfectants and algaecides not intended for direct application to humans or animals (Disinfectants) |
Where relevant, an exact description of the authorised use |
/ |
Target organism(s) (including development stage) |
Scientific name: bacteria Common name: Bacteria Development stage: Scientific name: viruses Common name: Viruses Development stage: |
Field(s) of use |
Indoor Outdoor Disinfection of waste water after the waste water plant, by shock dosing (in case of contamination). |
Application method(s) |
Method: Closed system Detailed description: Automated dosing system. |
Application rate(s) and frequency |
Application Rate: Shock dosing: 477 mg/l active chlorine (AC) under dirty conditions. Dilution (%): - Number and timing of application: Contact time: 30 minutes |
Category(ies) of users |
Industrial Professional |
Pack sizes and packaging material |
Cylinder: 4,8 - 140 l (6-175 kg Cl2) Drum: 400-1 000 l (500-1 250 kg Cl2) Railway tanks: 43 000 - 44 000 l (53 750 - 55 000 kg Cl2) Carbon/stainless steel |
4.1.1.
Use-specific instructions for use
4.1.2.
Use-specific risk mitigation measures
4.1.3.
Where specific to the use, the particulars of likely direct or indirect effects, first aid instructions and emergency measures to protect the environment
4.1.4.
Where specific to the use, the instructions for safe disposal of the product and its packaging
4.1.5.
Where specific to the use, the conditions of storage and shelf-life of the product under normal conditions of storage
4.2.
Use description
Product type |
PT05 - Drinking water (Disinfectants) |
Where relevant, an exact description of the authorised use |
/ |
Target organism(s) (including development stage) |
Scientific name: bacteria Common name: Bacteria Development stage: Scientific name: viruses Common name: Viruses Development stage: |
Field(s) of use |
Indoor Outdoor Disinfection at the drinking water suppliers and their water distribution systems, by continuous dosing. |
Application method(s) |
Method: Closed system Detailed description: Automated dosing system Adjustment applicable in the territory of the Federal Republic of Germany in accordance with Article 44(5) of Regulation (EU) No 528/2012: In accordance with the list of treatment substances and disinfection processes of paragraph 11 of the German Drinking Water Ordinance1, the technical rules for dosing set out in the Deutscher Verein des Gas Wasserfaches e.V2 -working sheets W 229, W 296, W 623 and the minimum contact time of W 229 apply3. (See section 6 for further references) |
Application rate(s) and frequency |
Application Rate: 0,5 mg/l active chlorine (AC) as residual concentration in the system Dilution (%): - Number and timing of application: Frequency: continuous dosing Adjustment applicable in the territory of the Federal Republic of Germany in accordance with Article 44 (5) of Regulation (EU) No 528/2012: In accordance with the list of treatment substances and disinfection processes of paragraph 11 of the German Drinking Water Ordinance (See section 6 for further reference)4 Application rate: Maximum addition 1,2 mg/l free Cl2; Concentration range after completion of treatment: maximum 0,3 mg/l free Cl2, minimum 0,1 mg/l free Cl2 (including the amounts before treatment and from other treatments) as residual concentration in the system In exceptional cases an addition of up to 6 mg/l free Cl2 and concentration of up to 0,6 mg/l free Cl2 after treatment is acceptable as residual concentration in the system, if disinfection cannot be ensured by other means or if disinfection is temporarily impaired by ammonium. |
Category(ies) of users |
Professional |
Pack sizes and packaging material |
Cylinder: 4,8 - 140 l (6-175 kg Cl2) Drum: 400-1 000 l (500-1 250 kg Cl2) Railway tanks: 43 000 - 44 000 l (53 750 - 55 000 kg Cl2) Carbon/stainless steel |
4.2.1.
Use-specific instructions for use
4.2.2.
Use-specific risk mitigation measures
4.2.3.
Where specific to the use, the particulars of likely direct or indirect effects, first aid instructions and emergency measures to protect the environment
4.2.4.
Where specific to the use, the instructions for safe disposal of the product and its packaging
4.2.5.
Where specific to the use, the conditions of storage and shelf-life of the product under normal conditions of storage
4.3.
Use description
Product type |
PT05 - Drinking water (Disinfectants) |
Where relevant, an exact description of the authorised use |
/ |
Target organism(s) (including development stage) |
Scientific name: bacteria Common name: Bacteria Development stage: Scientific name: viruses Common name: Viruses Development stage: |
Field(s) of use |
Indoor Outdoor Disinfection of water (with water coming from tap water network), in reservoirs/tanks, by continuous dosing. |
Application method(s) |
Method: Closed system Detailed description: Automated dosing system. The disinfection is carried out in the inlet of the reservoir, in order to assure proper distribution of the disinfectant in the water. Adjustment applicable in the territory of the Federal Republic of Germany in accordance with Article 44(5) of Regulation (EU) No 528/2012: In accordance with the list of treatment substances and disinfection processes of paragraph 11 of the German Drinking Water Ordinance1, the technical rules for dosing set out in the Deutscher DeutscherVerein des Gas Wasserfaches e.V2-working sheets W 229, W 296, W 623 and the minimum contact time of W 229 apply3. (See section 6 for further references) |
Application rate(s) and frequency |
Application Rate: 0,5 mg/l Active Chlorine (AC) as residual concentration in the system. Dilution (%): - Number and timing of application: Frequency: continuous dosing Adjustment applicable in the territory of the Federal Republic of Germany in accordance with Article 44(5) of Regulation (EU) No 528/2012 : In accordance with the list of treatment substances and disinfection processes of paragraph 11 of the German Drinking Water Ordinance1. (See section 6 for further reference)4. Application rate: maximum addition 1,2 mg/l free Cl2; Concentration range after completion of treatment: maximum 0,3 mg/l free Cl2, min 0,1 mg/L free Cl2 (including the amounts before treatment and from other treatments) In exceptional cases an addition of up to 6 mg/l free Cl2 and concentration up to 0,6 mg/l free Cl2 after treatment is acceptable, if disinfection cannot be ensured by other means or if disinfection is temporarily impaired by the presence of ammonium. |
Category(ies) of users |
Professional |
Pack sizes and packaging material |
Cylinder: 4,8 - 140 l (6-175 kg Cl2) Drum: 400-1 000 l (500-1 250 kg Cl2) Railway tanks: 43 000 - 44 000 l (53 750 - 55 000 kg Cl2) Carbon/stainless steel |
4.3.1.
Use-specific instructions for use
4.3.2.
Use-specific risk mitigation measures
4.3.3.
Where specific to the use, the particulars of likely direct or indirect effects, first aid instructions and emergency measures to protect the environment
4.3.4.
Where specific to the use, the instructions for safe disposal of the product and its packaging
4.3.5.
Where specific to the use, the conditions of storage and shelf-life of the product under normal conditions of storage
4.4.
Use description
Product type |
PT05 - Drinking water (Disinfectants) |
Where relevant, an exact description of the authorised use |
/ |
Target organism(s) (including development stage) |
Scientific name: bacteria Common name: Bacteria Development stage: Scientific name: viruses Common name: Viruses Development stage: Scientific name: legionella pneumophila Common name: Bacteria Development stage: |
Field(s) of use |
Indoor Outdoor In Public institutions, healthcare facilities Disinfection of drinking water in collective drinking water systems by continuous dosing |
Application method(s) |
Method: Closed system Detailed description: Automated dosing system Adjustment applicable in the territory of the Federal Republic of Germany in accordance with Article 44 (5) of Regulation (EU) No 528/2012: In accordance with the list of treatment substances and disinfection processes of paragraph 11 of the German Drinking Water Ordinance, the requirements set out in the Deutscher Verein des Gas Wasserfaches e.V2 -working sheets W 229, W 296, W 623 and the minimum contact time of W 229 apply3. (See section 6 for further references) |
Application rate(s) and frequency |
Application Rate: 1 mg/l active chlorine (AC) as residual concentration in the system Dilution (%): - Number and timing of application: Frequency: continuous dosing Adjustment applicable in the territory of the Federal Republic of Germany in accordance with Article 44 (5) of Regulation (EU) No 528/2012: In accordance with the list of treatment substances and disinfection processes of paragraph 11 of the German Drinking Water Ordinance1. (See section 6 for further reference)4 Application rate: maximum addition 1,2 mg/l free Cl2; Concentration range after completion of treatment: maximum 0,3 mg/l free Cl2, min 0,1 mg/L free Cl2 (including the amounts before treatment and from other treatments) In exceptional cases an addition of up to 6 mg/l free Cl2 and concentration up to 0,6 mg/l free Cl2 after treatment is acceptable, if disinfection cannot be ensured by other means or if disinfection is temporarily impaired by the presence of ammonium. |
Category(ies) of users |
Professional |
Pack sizes and packaging material |
Cylinder: 4,8 - 140 l (6-175 kg Cl2) Drum: 400-1 000 l (500-1 250 kg Cl2) Railway tanks: 43 000 - 44 000 l (53 750 - 55 000 kg Cl2) Carbon/stainless steel |
4.4.1.
Use-specific instructions for use
4.4.2.
Use-specific risk mitigation measures
4.4.3.
Where specific to the use, the particulars of likely direct or indirect effects, first aid instructions and emergency measures to protect the environment
4.4.4.
Where specific to the use, the instructions for safe disposal of the product and its packaging
4.4.5.
Where specific to the use, the conditions of storage and shelf-life of the product under normal conditions of storage
4.5.
Use description
Product type |
PT05 - Drinking water (Disinfectants) |
Where relevant, an exact description of the authorised use |
/ |
Target organism(s) (including development stage) |
Scientific name: bacteria Common name: Bacteria Development stage: Scientific name: viruses Common name: Viruses Development stage: |
Field(s) of use |
Indoor Outdoor Disinfection of drinking water for animals (with water coming from tap water network) in agricultural areas, by continuous dosing. |
Application method(s) |
Method: Closed system Detailed description: Automated dosing system |
Application rate(s) and frequency |
Application Rate: 0,5 mg/l active chlorine (AC) as residual concentration in the system. Dilution (%): - Number and timing of application: Frequency: continuous dosing |
Category(ies) of users |
Professional |
Pack sizes and packaging material |
Cylinder: 4,8 - 140 l (6-175 kg Cl2) Drum: 400-1 000 l (500-1 250 kg Cl2) Railway tanks: 43 000 - 44 000 l (53 750 – 55 000 kg Cl2) Carbon/stainless steel |