COMMISSION REGULATION (EU) No 548/2014
of 21 May 2014
on implementing Directive 2009/125/EC of the European Parliament and of the Council with regard to small, medium and large power transformers
Article 1
Subject matter and scope
Article 2
Definitions
Article 3
Eco-design requirements
Article 4
Conformity Assessment
Article 5
Verification procedure for market surveillance purposes
Article 6
Indicative Benchmarks
Article 7
Review
Article 8
Entry into force
ANNEX I
Ecodesign requirements
1.
Minimum energy performance or efficiency requirements for medium power transformers
1.1.
Requirements for three-phase medium power transformers with rated power ≤ 3 150 kVA
|
Tier 1 (from 1 July 2015) |
Tier 2 (from 1 July 2021) |
||
Rated Power (kVA) |
Maximum load losses Pk (W)(1) |
Maximum no-load losses Po (W)(1) |
Maximum load losses Pk (W)(1) |
Maximum no-load losses Po (W)(1) |
≤ 25 |
Ck (900) |
Ao (70) |
Ak (600) |
Ao – 10 % (63) |
50 |
Ck (1 100) |
Ao (90) |
Ak (750) |
Ao – 10 % (81) |
100 |
Ck (1 750) |
Ao (145) |
Ak (1 250) |
Ao – 10 % (130) |
160 |
Ck (2 350) |
Ao (210) |
Ak (1 750) |
Ao – 10 % (189) |
250 |
Ck (3 250) |
Ao (300) |
Ak (2 350) |
Ao – 10 % (270) |
315 |
Ck (3 900) |
Ao (360) |
Ak (2 800) |
Ao – 10 % (324) |
400 |
Ck (4 600) |
Ao (430) |
Ak (3 250) |
Ao – 10 % (387) |
500 |
Ck (5 500) |
Ao (510) |
Ak (3 900) |
Ao – 10 % (459) |
630 |
Ck (6 500) |
Ao (600) |
Ak (4 600) |
Ao – 10 % (540) |
800 |
Ck (8 400) |
Ao (650) |
Ak (6 000) |
Ao – 10 % (585) |
1 000 |
Ck (10 500) |
Ao (770) |
Ak (7 600) |
Ao – 10 % (693) |
1 250 |
Bk (11 000) |
Ao (950) |
Ak (9 500) |
Ao – 10 % (855) |
1 600 |
Bk (14 000) |
Ao (1 200) |
Ak (12 000) |
Ao – 10 % (1080) |
2 000 |
Bk (18 000) |
Ao (1 450) |
Ak (15 000) |
Ao – 10 % (1 305) |
2 500 |
Bk (22 000) |
Ao (1 750) |
Ak (18 500) |
Ao – 10 % (1 575) |
3 150 |
Bk (27 500) |
Ao (2 200) |
Ak (23 000) |
Ao – 10 % (1 980) |
|
Tier 1 (1 July 2015) |
Tier 2 (1 July 2021) |
||
Rated Power (kVA) |
Maximum load losses Pk (W)(2) |
Maximum no-load losses Po (W)(2) |
Maximum load losses Pk (W)(2) |
Maximum no-load losses Po (W)(2) |
≤ 50 |
Bk (1 700) |
Ao (200) |
Ak (1 500) |
Ao – 10 % (180) |
100 |
Bk (2 050) |
Ao (280) |
Ak (1 800) |
Ao – 10 % (252) |
160 |
Bk (2 900) |
Ao (400) |
Ak (2 600) |
Ao – 10 % (360) |
250 |
Bk (3 800) |
Ao (520) |
Ak (3 400) |
Ao – 10 % (468) |
400 |
Bk (5 500) |
Ao (750) |
Ak (4 500) |
Ao – 10 % (675) |
630 |
Bk (7 600) |
Ao (1 100) |
Ak (7 100) |
Ao – 10 % (990) |
800 |
Ak (8 000) |
Ao (1 300) |
Ak (8 000) |
Ao – 10 % (1 170) |
1 000 |
Ak (9 000) |
Ao (1 550) |
Ak (9 000) |
Ao – 10 % (1 395) |
1 250 |
Ak (11 000) |
Ao (1 800) |
Ak (11 000) |
Ao – 10 % (1 620) |
1 600 |
Ak (13 000) |
Ao (2 200) |
Ak (13 000) |
Ao – 10 % (1 980) |
2 000 |
Ak (16 000) |
Ao (2 600) |
Ak (16 000) |
Ao – 10 % (2 340) |
2 500 |
Ak (19 000) |
Ao (3 100) |
Ak (19 000) |
Ao – 10 % (2 790) |
3 150 |
Ak (22 000) |
Ao (3 800) |
Ak (22 000) |
Ao – 10 % (3 420) |
One winding with Um ≤ 24 kV and the other with Um > 1,1 kV |
The maximum allowable losses in Tables I.1 and I.2 shall be increased by 10 % for no load losses and by 10 % for load losses |
One winding with Um = 36 kV and the other with Um ≤ 1,1 kV |
The maximum allowable losses in Tables I.1 and I.2 shall be increased by 15 % for no load losses and by 10 % for load losses |
One winding with Um = 36 kV and the other with Um > 1,1 kV |
The maximum allowable losses indicated in Tables I.1 and I.2 shall be increased by 20 % for no load losses and by 15 % for load losses |
Case of dual voltage on one winding |
In case of transformers with one high-voltage winding and two voltages available from a tapped low-voltage winding, losses shall be calculated based on the higher voltage of the low-voltage winding and shall be in compliance with the maximum allowable losses in Tables I.1 and 1.2. The maximum available power on the lower voltage of the low-voltage winding on such transformers shall be limited to 0,85 of the rated power assigned to the low-voltage winding at its higher voltage. |
In case of transformers with one low-voltage winding with two voltages available from a tapped high-voltage winding, losses shall be calculated based on the higher voltage of the high-voltage winding and shall be in compliance with the maximum allowable losses in Tables I.1 and I.2., The maximum available power on the lower voltage of the high-voltage winding on such transformer shall be limited to 0,85 of the rated power assigned to the high-voltage winding at its higher voltage. |
|
If the full nominal power is available regardless of the combination of voltages, the levels of losses indicated in Tables I.1 and I.2 can be increased by 15 % for no load losses and by 10 % for load losses. |
|
Case of dual voltage on both windings |
The maximum allowable losses in Tables I.1 and I.2 can be increased by 20 % for no load losses and by 20 % for load losses for transformers with dual voltage on both windings. The level of losses is given for the highest possible rated power and on the basis that the rated power is the same regardless of the combination of voltages. |
1.2.
Requirements for medium power transformers with rated power > 3 150 kVA
Rated Power (kVA) |
Tier 1 (1 July 2015) |
Tier 2 (1 July 2021) |
Minimum Peak Efficiency Index (%) |
||
3 150 < Sr ≤ 4 000 |
99,465 |
99,532 |
5 000 |
99,483 |
99,548 |
6 300 |
99,510 |
99,571 |
8 000 |
99,535 |
99,593 |
10 000 |
99,560 |
99,615 |
12 500 |
99,588 |
99,640 |
16 000 |
99,615 |
99,663 |
20 000 |
99,639 |
99,684 |
25 000 |
99,657 |
99,700 |
31 500 |
99,671 |
99,712 |
40 000 |
99,684 |
99,724 |
Rated Power (kVA) |
Tier 1 (1 July 2015) |
Tier 2 (1 July 2021) |
Minimum Peak Efficiency Index (%) |
||
3 150 < Sr ≤ 4 000 |
99,348 |
99,382 |
5 000 |
99,354 |
99,387 |
6 300 |
99,356 |
99,389 |
8 000 |
99,357 |
99,390 |
≥ 10 000 |
99,357 |
99,390 |
1.3.
Requirements for medium power transformers with rated power ≤ 3 150 kVA equipped with tapping connections suitable for operation while being energised or on-load for voltage adaptation purposes. Voltage Regulation Distribution Transformers are included in this category.
1.4.
Requirements for medium power pole-mounted transformers
|
Tier 1 (1 July 2015) |
Tier 2 (1 July 2021) |
||
Rated Power (kVA) |
Maximum load losses (in W)(3) |
Maximum no-load losses (in W)(3) |
Maximum load losses (in W)(3) |
Maximum no-load losses (in W)(3) |
25 |
Ck (900) |
Ao (70) |
Bk (725) |
Ao (70) |
50 |
Ck (1 100) |
Ao (90) |
Bk (875) |
Ao (90) |
100 |
Ck (1 750) |
Ao (145) |
Bk (1 475) |
Ao (145) |
160 |
Ck + 32 % (3 102) |
Co (300) |
Ck + 32 % (3 102) |
Co – 10 % (270) |
200 |
Ck (2 750) |
Co (356) |
Bk (2 333) |
Bo (310) |
250 |
Ck (3 250) |
Co (425) |
Bk (2 750) |
Bo (360) |
315 |
Ck (3 900) |
Co (520) |
Bk (3 250) |
Bo (440) |
2.
Minimum energy efficiency requirements for large power transformers
Rated Power (MVA) |
Tier 1 (1 July 2015) |
Tier 2 (1 July 2021) |
Minimum Peak Efficiency Index (%) |
||
≤ 4 |
99,465 |
99,532 |
5 |
99,483 |
99,548 |
6,3 |
99,510 |
99,571 |
8 |
99,535 |
99,593 |
10 |
99,560 |
99,615 |
12,5 |
99,588 |
99,640 |
16 |
99,615 |
99,663 |
20 |
99,639 |
99,684 |
25 |
99,657 |
99,700 |
31,5 |
99,671 |
99,712 |
40 |
99,684 |
99,724 |
50 |
99,696 |
99,734 |
63 |
99,709 |
99,745 |
80 |
99,723 |
99,758 |
≥ 100 |
99,737 |
99,770 |
Rated Power (MVA) |
Tier 1 (1 July 2015) |
Tier 2 (1 July 2021) |
Minimum Peak Efficiency Index (%) |
||
≤ 4 |
99,158 |
99,225 |
5 |
99,200 |
99,265 |
6,3 |
99,242 |
99,303 |
8 |
99,298 |
99,356 |
10 |
99,330 |
99,385 |
12,5 |
99,370 |
99,422 |
16 |
99,416 |
99,464 |
20 |
99,468 |
99,513 |
25 |
99,521 |
99,564 |
31,5 |
99,551 |
99,592 |
40 |
99,567 |
99,607 |
50 |
99,585 |
99,623 |
≥ 63 |
99,590 |
99,626 |
3.
Product information requirements
4.
Technical documentation
ANNEX II
Measurement and calculation methods
Measurement method
Calculation methods
ANNEX III
Verification procedure
Measured parameter |
Verification tolerances |
Load losses |
The measured value shall not be greater than the declared value by more than 5 %. |
No load losses |
The measured value shall not be greater than the declared value by more than 5 %. |
The electrical power required by the cooling system for no load operation |
The measured value shall not be greater than the declared value by more than 5 %. |