COMMISSION REGULATION (EU) 2015/1095
of 5 May 2015
implementing Directive 2009/125/EC of the European Parliament and of the Council with regard to ecodesign requirements for professional refrigerated storage cabinets, blast cabinets, condensing units and process chillers
(Text with EEA relevance)
Article 1
Subject matter and scope
Article 2
Definitions
Article 3
Ecodesign requirements and timetable
Article 4
Conformity assessment
Article 5
Verification procedure for market surveillance purposes
Article 6
Indicative benchmarks
Article 7
Review
Article 8
Entry into force
ANNEX I
Definitions applicable for Annexes II to XII
Definitions related to professional refrigerated storage cabinets and blast cabinets
Definitions related to condensing units
Definitions related to process chillers
Common definitions:
ANNEX II
Ecodesign requirements for professional refrigerated storage cabinets and blast cabinets
1. REQUIREMENTS FOR ENERGY EFFICIENCY
2. REQUIREMENTS FOR PRODUCT INFORMATION
Model(s): [information identifying the model(s) to which the information relates] |
|||||
Intended use |
storage |
||||
Operating temperature(s) |
chilled/frozen/multi-use |
||||
Category |
Vertical/counter |
||||
(where applicable) Heavy-duty/light-duty |
|||||
Refrigerant fluid(s): [information to identify the refrigerant fluid(s), including GWP] |
|||||
Item |
Symbol |
Value |
Unit |
||
Annual Energy Consumption |
AEC |
x,xx |
kWh |
||
Energy Efficiency Index |
EEI |
x,xx |
|
||
Net volume |
VN |
x,x |
litre |
||
(where applicable) |
|
|
|
||
Chilled volume |
VNRef |
x,x |
litre |
||
Frozen volume |
VNFrz |
x,x |
litre |
||
Refrigerant charge |
|
x,xx |
kg |
||
Contact details |
Name and address of the manufacturer or its authorised representative. |
ANNEX III
Method for calculating the energy efficiency index for professional refrigerated storage cabinets
Category |
Value for M |
Value for N |
Vertical Chilled |
1,643 |
609 |
Vertical Frozen |
4,928 |
1 472 |
Counter Chilled |
2,555 |
1 790 |
Counter Frozen |
5,840 |
2 380 |
ANNEX IV
Measurements and calculations for professional refrigerated storage cabinets
Test room climate class |
Dry bulb temperature, °C |
Relative humidity, % |
Dew point, °C |
Water vapour mass in dry air, g/kg |
3 |
25 |
60 |
16,7 |
12,0 |
4 |
30 |
55 |
20,0 |
14,8 |
5 |
40 |
40 |
23,9 |
18,8 |
ANNEX V
Ecodesign requirements for condensing units
1. REQUIREMENTS FOR ENERGY EFFICIENCY
Operating temperature |
Rated capacity PA |
Applicable ratio |
Value |
Medium |
0,2 kW≤ PA ≤ 1 kW |
COP |
1,20 |
1 kW< PA ≤ 5 kW |
COP |
1,40 |
|
5 kW < PA ≤ 20 kW |
SEPR |
2,25 |
|
20 kW < PA ≤ 50 kW |
SEPR |
2,35 |
|
Low |
0,1 kW≤ PA ≤ 0,4 kW |
COP |
0,75 |
0,4 kW< PA ≤ 2 kW |
COP |
0,85 |
|
2 kW < PA ≤ 8kW |
SEPR |
1,50 |
|
8 kW < PA ≤ 20 kW |
SEPR |
1,60 |
Operating temperature |
Rated capacity PA |
Applicable ratio |
Value |
Medium |
0,2 kW≤ PA ≤ 1kW |
COP |
1,40 |
1 kW< PA ≤ 5 kW |
COP |
1,60 |
|
5 kW < PA ≤ 20 kW |
SEPR |
2,55 |
|
20 kW < PA ≤ 50 kW |
SEPR |
2,65 |
|
Low |
0,1 kW≤ PA ≤ 0,4 kW |
COP |
0,80 |
0,4 kW< PA ≤ 2 kW |
COP |
0,95 |
|
2 kW < PA ≤ 8 kW |
SEPR |
1,60 |
|
8 kW < PA ≤ 20 kW |
SEPR |
1,70 |
2. REQUIREMENTS FOR PRODUCT INFORMATION
Model(s): [information identifying the model(s) to which the information relates] |
||||||
Refrigerant fluid(s): [information to identify the refrigerant fluid(s) intended to be used with the condensing unit] |
||||||
Item |
Symbol |
Value |
Unit |
|||
Evaporating temperature (1) |
t |
– 10 °C |
– 35 °C |
°C |
||
Parameters at full load and ambient temperature 32 °C |
||||||
Rated cooling capacity |
PA |
x,xxx |
x,xxx |
kW |
||
Rated power input |
DA |
x,xxx |
x,xxx |
kW |
||
Rated COP |
COPA |
x,xx |
x,xx |
|
||
Parameters at full load and ambient temperature 25 °C |
||||||
Cooling capacity |
P2 |
x,xxx |
x,xxx |
kW |
||
Power input |
D2 |
x,xxx |
x,xxx |
kW |
||
COP |
COP2 |
x,xx |
x,xx |
|
||
Parameters at full load and ambient temperature 43 °C (where applicable) |
||||||
Cooling capacity |
P3 |
x,xxx |
x,xxx |
kW |
||
Power input |
D3 |
x,xxx |
x,xxx |
kW |
||
COP |
COP3 |
x,xx |
x,xx |
|
||
Other items |
||||||
Capacity control |
fixed/step/variable |
|||||
Contact details |
Name and address of the manufacturer or its authorised representative. |
Model(s): [information identifying the model(s) to which the information relates] |
|||||
Refrigerant fluid(s): [information to identify the refrigerant fluid(s) intended to be used with the condensing unit] |
|||||
Item |
Symbol |
Value |
Unit |
||
Evaporating temperature (2) |
t |
– 10 °C |
– 35 °C |
°C |
|
Annual electricity consumption |
Q |
x |
x |
kWh/a |
|
Seasonal energy performance ratio |
SEPR |
x,xx |
x,xx |
|
|
Parameters at full load and ambient temperature 32 °C (point (A) |
|||||
Rated cooling capacity |
PA |
x,xx |
x,xx |
kW |
|
Rated power input |
DA |
x,xx |
x,xx |
kW |
|
Rated COP |
COPA |
x,xx |
x,xx |
|
|
Parameters at part load and ambient temperature 25 °C (point (B) |
|||||
Declared cooling capacity |
PB |
x,xx |
x,xx |
kW |
|
Declared power input |
DB |
x,xx |
x,xx |
kW |
|
Declared COP |
COPB |
x,xx |
x,xx |
|
|
Parameters at part load and ambient temperature 15 °C (point (C) |
|||||
Declared cooling capacity |
Pc |
x,xx |
x,xx |
kW |
|
Declared power input |
Dc |
x,xx |
x,xx |
kW |
|
Declared COP |
COPC |
x,xx |
x,xx |
|
|
Parameters at part load and ambient temperature 5 °C (point (D) |
|||||
Declared cooling capacity |
PD |
x,xx |
x,xx |
kW |
|
Declared power input |
DD |
x,xx |
x,xx |
kW |
|
Declared COP |
COPD |
x,xx |
x,xx |
|
|
Parameters at full load and ambient temperature 43 °C (where applicable) |
|||||
Cooling capacity |
P3 |
x,xx |
x,xx |
kW |
|
Power input |
D3 |
x,xx |
x,xx |
kW |
|
Declared COP |
COP3 |
x,xx |
x,xx |
|
|
Other items |
|||||
Capacity control |
fixed/step/variable |
||||
Degradation coefficient for fixed and staged capacity units |
Cdc |
0,25 |
|
||
Contact details |
Name and address of the manufacturer or its authorised representative. |
ANNEX VI
Measurements and calculations for condensing units
j |
Tj |
hj |
1 |
– 19 |
0,08 |
2 |
– 18 |
0,41 |
3 |
– 17 |
0,65 |
4 |
– 16 |
1,05 |
5 |
– 15 |
1,74 |
6 |
– 14 |
2,98 |
7 |
– 13 |
3,79 |
8 |
– 12 |
5,69 |
9 |
– 11 |
8,94 |
10 |
– 10 |
11,81 |
11 |
– 9 |
17,29 |
12 |
– 8 |
20,02 |
13 |
– 7 |
28,73 |
14 |
– 6 |
39,71 |
15 |
– 5 |
56,61 |
16 |
– 4 |
76,36 |
17 |
– 3 |
106,07 |
18 |
– 2 |
153,22 |
19 |
– 1 |
203,41 |
20 |
0 |
247,98 |
21 |
1 |
282,01 |
22 |
2 |
275,91 |
23 |
3 |
300,61 |
24 |
4 |
310,77 |
25 |
5 |
336,48 |
26 |
6 |
350,48 |
27 |
7 |
363,49 |
28 |
8 |
368,91 |
29 |
9 |
371,63 |
30 |
10 |
377,32 |
31 |
11 |
376,53 |
32 |
12 |
386,42 |
33 |
13 |
389,84 |
34 |
14 |
384,45 |
35 |
15 |
370,45 |
36 |
16 |
344,96 |
37 |
17 |
328,02 |
38 |
18 |
305,36 |
39 |
19 |
261,87 |
40 |
20 |
223,90 |
41 |
21 |
196,31 |
42 |
22 |
163,04 |
43 |
23 |
141,78 |
44 |
24 |
121,93 |
45 |
25 |
104,46 |
46 |
26 |
85,77 |
47 |
27 |
71,54 |
48 |
28 |
56,57 |
49 |
29 |
43,35 |
50 |
30 |
31,02 |
51 |
31 |
20,21 |
52 |
32 |
11,85 |
53 |
33 |
8,17 |
54 |
34 |
3,83 |
55 |
35 |
2,09 |
56 |
36 |
1,21 |
57 |
37 |
0,52 |
58 |
38 |
0,40 |
ANNEX VII
Ecodesign requirements for process chillers
1. REQUIREMENTS FOR ENERGY EFFICIENCY
Heat transfer medium at the condensing side |
Operating temperature |
Rated cooling capacity PA |
Minimum SEPR value |
Air |
Medium |
PA ≤ 300 kW |
2,24 |
PA > 300 kW |
2,80 |
||
Low |
PA ≤ 200 kW |
1,48 |
|
PA > 200 kW |
1,60 |
||
Water |
Medium |
PA ≤ 300 kW |
2,86 |
PA > 300 kW |
3,80 |
||
Low |
PA ≤ 200 kW |
1,82 |
|
PA > 200 kW |
2,10 |
Heat transfer medium at the condensing side |
Operating temperature |
Rated cooling capacity PA |
Minimum SEPR value |
Air |
Medium |
PA ≤ 300 kW |
2,58 |
PA > 300 kW |
3,22 |
||
Low |
PA ≤ 200 kW |
1,70 |
|
PA > 200 kW |
1,84 |
||
Water |
Medium |
PA ≤ 300 kW |
3,29 |
PA > 300 kW |
4,37 |
||
Low |
PA ≤ 200 kW |
2,09 |
|
PA > 200 kW |
2,42 |
2. REQUIREMENTS FOR PRODUCT INFORMATION
Model(s): [information identifying the model(s) to which the information relates] |
||||||
Type of condensing: [air-cooled/water-cooled] |
||||||
Refrigerant fluid(s): [information identifying the refrigerant fluid(s) intended to be used with the process chiller] |
||||||
Item |
Symbol |
Value |
Unit |
|||
Operating temperature |
t |
– 8 °C |
– 25 °C |
°C |
||
Seasonal Energy Performance Ratio |
SEPR |
x,xx |
x,xx |
|
||
Annual electricity consumption |
Q |
x |
x |
kWh/a |
||
Parameters at full load and reference ambient temperature (point (A) |
||||||
Rated cooling capacity |
PA |
x,xx |
x,xx |
kW |
||
Rated power input |
DA |
x,xx |
x,xx |
kW |
||
Rated EER |
EERA |
x,xx |
x,xx |
|
||
Parameters at rating point B |
||||||
Declared cooling capacity |
PB |
x,xx |
x,xx |
kW |
||
Declared power input |
DB |
x,xx |
x,xx |
kW |
||
Declared EER |
EERB |
x,xx |
x,xx |
|
||
Parameters at rating point C |
||||||
Declared cooling capacity |
Pc |
x,xx |
x,xx |
kW |
||
Declared power input |
Dc |
x,xx |
x,xx |
kW |
||
Declared EER |
EERC |
x,xx |
x,xx |
|
||
Parameters at rating point D |
||||||
Declared cooling capacity |
PD |
x,xx |
x,xx |
kW |
||
Declared power input |
DD |
x,xx |
x,xx |
kW |
||
Declared EER |
EERD |
x,xx |
x,xx |
|
||
Other items |
||||||
Capacity control |
|
fixed/staged(2)/variable |
||||
Degradation coefficient for fixed and staged capacity units(1) |
Cc |
x,xx |
x,xx |
|
||
Contact details |
Name and address of the manufacturer or its authorised representative. |
ANNEX VIII
Measurements and calculations for process chillers
ANNEX IX
Verification procedure for market surveillance purposes for professional refrigerated storage cabinets
ANNEX X
Verification procedure for market surveillance purposes for condensing units
ANNEX XI
Verification procedure for market surveillance purposes for process chillers
ANNEX XII
Indicative benchmarks referred to in Article 6
|
Net volume (litres) |
Annual energy consumption |
EEI |
Chilled vertical |
600 |
474,5 |
29,7 |
Chilled counter |
300 |
547,5 |
21,4 |
Frozen vertical |
600 |
1 825 |
41,2 |
Frozen counter |
200 |
1 460 |
41,0 |
Operating temperature |
Rated capacity PA |
Applicable ratio |
Benchmark value |
Medium |
0,2 kW ≤ PA ≤ 1 kW |
COP |
1,9 |
1 kW < PA ≤ 5 kW |
COP |
2,3 |
|
5 kW < PA ≤ 20 kW |
SEPR |
3,6 |
|
20 kW < PA ≤ 50 kW |
SEPR |
3,5 |
|
Low |
0,1 kW ≤ PA ≤ 0,4 kW |
COP |
1,0 |
0,4 kW < PA ≤ 2 kW |
COP |
1,3 |
|
2 kW < PA ≤ 8 kW |
SEPR |
2,0 |
|
8 kW < PA ≤ 20 kW |
SEPR |
2,0 |
Heat transfer medium at the condensing side |
Operating temperature |
Rated cooling capacity PA |
Minimum SEPR value |
Air |
Medium |
PA ≤ 300 kW |
3,4 |
PA > 300 kW |
3,7 |
||
Low |
PA ≤ 200 kW |
1,9 |
|
PA > 200 kW |
1,95 |
||
Water |
Medium |
PA ≤ 300 kW |
4,3 |
PA > 300 kW |
4,5 |
||
Low |
PA ≤ 200 kW |
2,3 |
|
PA > 200 kW |
2,7 |