COMMISSION REGULATION (EU) 2019/424
of 15 March 2019
laying down ecodesign requirements for servers and data storage products pursuant to Directive 2009/125/EC of the European Parliament and of the Council and amending Commission Regulation (EU) No 617/2013
(Text with EEA relevance)
Article 1
Subject matter and scope
Article 2
Definitions
Article 3
Ecodesign requirements and timetable
Article 4
Conformity assessment
Article 5
Verification procedure for market surveillance purposes
Article 6
Circumvention
Article 7
Indicative benchmarks
Article 8
Review
Article 9
Amendment to Regulation (EU) No 617/2013
‘Article 3
Ecodesign requirements
Article 10
Entry into force
ANNEX I
Definitions applicable to Annexes II to V
ANNEX II
Ecodesign requirements
1. SPECIFIC ECODESIGN REQUIREMENTS FOR SERVERS AND ONLINE DATA STORAGE PRODUCTS
1.1.
PSU efficiency and power factor requirements
|
Minimum PSU efficiency |
Minimum power factor |
|||
% of rated load |
10 % |
20 % |
50 % |
100 % |
50 % |
Multi output |
— |
88 % |
92 % |
88 % |
0,90 |
Single output |
— |
90 % |
94 % |
91 % |
0,95 |
|
Minimum PSU efficiency |
Minimum power factor |
|||
% of rated load |
10 % |
20 % |
50 % |
100 % |
50 % |
Multi output |
— |
90 % |
94 % |
91 % |
0,95 |
Single output |
90 % |
94 % |
96 % |
91 % |
0,95 |
1.2.
Material efficiency requirements
2. SPECIFIC ECODESIGN REQUIREMENTS ONLY FOR SERVERS WITH ONE OR TWO PROCESSOR SOCKETS
2.1.
Idle state power
Product type |
Base idle state power allowance, Pbase (W) |
1-socket servers (neither blade nor multi-node servers) |
25 |
2-socket servers (neither blade nor multi-node servers) |
38 |
Blade or multi-node servers |
40 |
System characteristics |
Applies to |
Additional idle power allowance |
CPU Performance |
All servers |
1 socket: 10 × PerfCPU W 2 socket: 7 × PerfCPU W |
Additional PSU |
PSU installed explicitly for power redundancy |
10 W per PSU |
HDD or SSD |
Per installed HDD or SSD |
5,0 W per HDD or SSD |
Additional memory |
Installed memory greater than 4 GB |
0,18 W per GB |
Additional buffered DDR channel |
Installed buffered DDR channels greater than 8 channels |
4,0 W per buffered DDR channel |
Additional I/O devices |
Installed devices greater than two ports of ≥ 1 Gbit, onboard Ethernet |
< 1 Gb/s: No Allowance |
= 1 Gb/s: 2,0 W/Active Port |
||
> 1 Gb/s and < 10 Gb/s: 4,0 W/Active Port |
||
≥ 10 Gb/s and < 25Gb/s: 15,0 W/Active Port |
||
≥ 25 Gb/s and < 50Gb/s: 20,0 W/Active Port |
||
≥ 50 Gb/s 26,0 W/Active Port |
2.2.
Active state efficiency
Product type |
Minimum active state efficiency |
1-socket servers |
9,0 |
2-socket servers |
9,5 |
Blade or multi-node servers |
8,0 |
3. INFORMATION TO BE PROVIDED BY MANUFACTURERS
|
Dry bulb temp °C |
Humidity range, non-condensing |
|
|
||
Operating condition class |
Allowable range |
Recommended range |
Allowable range |
Recommended range |
Max dew point (°C) |
Maximum rate of change (°C/hr) |
A1 |
15- 32 |
18-27 |
– 12 °C Dew Point (DP) and 8 % relative humidity (RH) to 17 °C DP and 80 % RH |
– 9 °C DP to 15 °C DP and 60 % RH |
17 |
5/20 |
A2 |
10-35 |
18-27 |
– 12 °C DP and 8 % RH to 21 °C DP and 80 % RH |
Same as A1 |
21 |
5/20 |
A3 |
5-40 |
18-27 |
– 12 °C DP and 8 % RH to 24 °C DP and 85 % RH |
Same as A1 |
24 |
5/20 |
A4 |
5-45 |
18-27 |
– 12 °C DP and 8 % RH to 24 °C DP and 90 % RH |
Same as A1 |
24 |
5/20 |
ANNEX III
Measurements and calculations
ANNEX IV
Verification procedure for market surveillance purposes
Parameters |
Verification tolerances |
PSU efficiency (%) |
The determined value shall not be lower than the declared value by more than 2 %. |
Power factor |
The determined value shall not be lower than the declared value by more than 10 %. |
Idle state power, Pidle and maximum power (W) |
The determined value shall not exceed the declared value by more than 10 %. |
Active state efficiency and performance in active state |
The determined value shall not be lower than the declared value by more than 10 %. |
ANNEX V
Indicative benchmarks referred to in Article 6
Product type |
Idle power, W |
Active state efficiency |
Operating condition class |
Tower server, 1 socket |
21,3 |
17 |
A3 |
Rack server, 1 socket |
18 |
17,7 |
A4 |
Rack server, 2 socket, low performance |
49,9 |
18 |
A4 |
Rack server, 2 socket, high performance |
67 |
26,1 |
A4 |
Rack server, 4 socket |
65,1 |
34,8 |
A4 |
Blade server, 2 socket |
75 |
47,3 |
A3 |
Blade server, 4 socket |
63,3 |
21,9 |
A3 |
Resilient server, 2 socket |
222 |
9,6 |
A3 |
Data storage products |
Not applicable |
Not applicable |
A3 |
PSU nameplate power |
10 % |
20 % |
50 % |
100 % |
< 750W |
91,17 % |
93,76 % |
94,72 % Power factor > 0,95 |
94,14 % |
≥ 750W |
95,02 % |
95,99 % Power factor > 0,95 |
96,09 % |
94,69 % |